Live loads for houses in Pakistan (Building Code of Pakistan 2021)
BetaThe minimum live loads the Building Code of Pakistan 2021 gives for houses, flats, stairs, balconies, garages and roofs, with the Table 1607.1 item for every value, the partition rule, and a worked example of the load on a load-bearing brick wall in a two-storey house with RC slabs.
Updated 18 October 2026
What BCP 2021 covers
The Building Code of Pakistan (BCP) 2021 is published by the Pakistan Engineering Council (PEC). It revises the Building Code of Pakistan – Seismic Provisions 2007, which was notified by S.R.O. 971(I)/2008, and it is based on the 2021 International Building Code (IBC), used under a licence from the International Code Council. It keeps the IBC's chapter and section numbers, so Chapter 16 (Structural Design) reads like IBC Chapter 16, with Pakistan's own ground snow, wind speed, rainfall, flood and earthquake maps added.
Section 1607 and Table 1607.1 give the minimum uniformly distributed live loads, Lo, and the concentrated loads for each occupancy or use. Use the larger of the load the intended use is expected to cause and the table value (1607.3). The table is in pounds per square foot (psf), with the SI note 1 psf = 0.0479 kN/m². This page gives kN/m² first and the psf table value in brackets, as the app does.
For load combinations, wind, snow and earthquake, BCP 2021 points to ASCE/SEI 7-16 (Minimum Design Loads and Associated Criteria for Buildings and Other Structures), as the IBC does. Section 1605.1 lets you use the strength combinations of ASCE 7 Section 2.3, the allowable stress combinations of ASCE 7 Section 2.4, or the alternative allowable stress combinations printed in BCP Section 1605.2.
Detached one- and two-family houses and townhouses of up to three storeys above grade, with their own exit, may comply with BCP 2021 or with the International Residential Code (101.2, exception). Where a house is designed by an engineer to BCP Chapter 16, the values below apply. Check with the local building control authority which rules it applies.
Live loads for houses (Table 1607.1)
| Table 1607.1 item | Use | Load, kN/m² (psf) | Notes |
|---|---|---|---|
| 26, one- and two-family dwellings | All other areas: rooms, kitchens, corridors in a house | 1.92 (40) | |
| 26, one- and two-family dwellings | Habitable attics and sleeping areas | 1.44 (30) | Also attics served by a fixed stair, not a pull-down stair (1607.22.3) |
| 26, one- and two-family dwellings | Uninhabitable attics with storage | 0.96 (20) | Only where the access and slope limits of 1607.22.2 are met; elsewhere at least 0.48 (10) |
| 26, one- and two-family dwellings | Uninhabitable attics without storage | 0.48 (10) | Need not act with any other live load (1607.22.1) |
| 26, one- and two-family dwellings | Canopies, including marquees | 0.96 (20) | Also design for snow and wind (1607.14.3) |
| 26, hotels and multifamily dwellings | Private rooms and corridors serving them (flats) | 1.92 (40) | |
| 26, hotels and multifamily dwellings | Public rooms and corridors serving them | 4.79 (100) | No live load reduction for public rooms (note a) |
| 31, stairs and exits | One- and two-family dwellings | 1.92 (40) | All other stairs and exits: 4.79 (100) |
| 5, balconies and decks | Balconies and decks | 1.5 × the area served | Need not exceed 4.79 (100). Off a house's rooms: 1.5 × 40 psf = 60 psf, 2.87 kN/m² |
| 13, fire escapes | On single-family dwellings only | 1.92 (40) | Other fire escapes: 4.79 (100) |
| 15, garages | Passenger vehicles only | 1.92 (40) | Or the 3,000 lb concentrated load of 1607.7, whichever governs; no reduction except up to 20% for members supporting two or more floors (note c) |
| 32 | Storage areas above ceilings | 0.96 (20) | |
| 27, roofs | Ordinary flat, pitched and curved roofs, not occupiable | 0.96 (20) | Roof live load Lr; may be reduced by 1607.14.2.1 to between 0.58 and 0.96 (12 and 20) |
| 27, roofs | Roof areas used for occupancies other than assembly | Same as the occupancy served | A house roof used by the household: 1.92 (40). May be reduced by 1607.12 (1607.14.2.2) |
| 37 | Yards and terraces, pedestrian | 4.79 (100) | No live load reduction (note a) |
These are minimums (1607.3). Floors must also carry the concentrated loads of Table 1607.1 where the table gives one, whichever has the worse effect (1607.4); for dwellings the table gives none except 300 lb on stair treads. Floor live loads may be reduced for large tributary areas by 1607.12; no reduction is applied on this page.
Partitions (1607.5)
In buildings where partition positions may change, BCP 2021 treats partitions as a live load: allow at least 0.72 kN/m² (15 psf) uniformly distributed, whether or not partitions are shown on the drawings, unless the specified live load is 4.79 kN/m² (80 psf) or more (1607.5). The house live load of 1.92 kN/m² is below that limit, so the allowance applies to light partitions that could be moved.
Fixed brick or block partitions are not movable, so take them as dead load at their actual weight (1606.2), placed where they stand. A 115 mm brick partition on a slab is much heavier than 0.72 kN/m² spread over the floor, so model it as a line load on the slab or on the beam or wall below.
Interior walls and partitions over 1.83 m (6 ft) high must also resist a horizontal load of at least 0.240 kN/m² (5 psf) (1607.16).
Roofs
A flat RC roof that nobody uses takes the ordinary roof live load of 0.96 kN/m² (20 psf), on the horizontal projection, which 1607.14.2.1 lets you reduce for large tributary areas or steep slopes. Most flat roofs on Pakistani houses are reached by a stair and used for sleeping, drying clothes and water tanks: treat them as occupiable and use the load of the occupancy served, 1.92 kN/m² (40 psf), as floor live load L. Add the weight of water tanks as dead load. Snow is only a design load where BCP Figures 1608.2(1) and 1608.2(2) or a site study give a ground snow load; it may be taken as zero where no snow is reported, as the authority approves (1608.2).
Example: load-bearing brick wall in a two-storey RC-slab house
A two-storey house of load-bearing brick walls with cast-in-place RC slabs, a common form in Pakistan. A 225 mm (9 in) interior brick wall runs the length of the house. The first-floor slab and the roof slab each span 3.6 m one way from the exterior walls onto this wall, on both sides, so the wall's tributary width is 3.6 / 2 + 3.6 / 2 = 3.6 m (simple spans; continuity over the wall would raise this). The roof is reached by a stair and used by the household. Wall height between slabs 3.0 m in each storey.
Assumed dead loads (check them for the actual build-up; BCP 2021 asks for actual weights, 1606.2, and gives no table of material weights): RC slab 150 mm at 24 kN/m³ = 3.6 kN/m²; floor finish, screed and ceiling plaster 1.2 kN/m²; roof insulation and waterproofing (mud phuska and brick tiles) with ceiling plaster 2.4 kN/m²; 225 mm brick wall plastered both sides 4.8 kN/m² of wall area. Live loads from Table 1607.1: first floor 1.92 kN/m² (40 psf, item 26, all other areas); roof used by the household 1.92 kN/m² (40 psf, item 27, same as the occupancy served).
| Item | Working | Dead D (kN/m) | Live L (kN/m) |
|---|---|---|---|
| Roof slab | (3.6 + 2.4) kN/m² × 3.6 m; 1.92 kN/m² × 3.6 m | 21.60 | 6.91 |
| First-floor wall | 3.0 m × 4.8 kN/m² | 14.40 | – |
| First-floor slab | (3.6 + 1.2) kN/m² × 3.6 m; 1.92 kN/m² × 3.6 m | 17.28 | 6.91 |
| Ground-floor wall | 3.0 m × 4.8 kN/m² | 14.40 | – |
| Total | 67.68 | 13.82 |
Factored and service loads
Strength combinations from ASCE 7-16 Section 2.3, which BCP 1605.1 refers to (BCP itself does not print them): 1.4D = 1.4 × 67.68 = 94.8 kN/m. 1.2D + 1.6L = 1.2 × 67.68 + 1.6 × 13.82 = 81.2 + 22.1 = 103.3 kN/m. The second governs. Its 0.5(Lr or S or R) term is zero here, because the used roof carries floor live load L, not roof live load Lr. Use 103.3 kN/m to check the brickwork in compression to TMS 402, which BCP 2101.2 refers to, and the strength design of the footing.
Service load, BCP 1605.2 Equation 16-1, D + L + (Lr or S or R): 67.68 + 13.82 = 81.5 kN/m. Use it with the soil's allowable bearing pressure to size the strip footing.
Add the plinth wall and the footing's own weight below ground-floor level. This is a gravity check only: brick walls in Pakistan must also be checked for earthquake load under BCP Section 1613 and ASCE 7, which this example does not cover. No live load reduction is applied.
Common mistakes
- Using the 2007 code's live load table. BCP 2021 Table 1607.1 replaces it; take values from the 2021 table.
- Designing a flat roof that the household uses for 0.96 kN/m² (20 psf). A used roof takes the load of the occupancy served, 1.92 kN/m² (40 psf) for a house.
- Spreading fixed brick partitions as the 0.72 kN/m² (15 psf) allowance. That allowance is for movable partitions; heavy fixed partitions are dead load at their actual weight and position.
- Using 1.92 kN/m² for a balcony. Balconies and decks take 1.5 times the load of the area they serve, 2.87 kN/m² (60 psf) off a house's rooms.
- Mixing units: Table 1607.1 is in psf. 40 psf is 1.92 kN/m², not 4 kN/m² or 40 kN/m².
- Checking footing bearing pressure with factored loads, or the brickwork with service loads. Keep factored (ASCE 7 Section 2.3) and service (BCP 1605.2) totals apart.
Do this on your own plans
LoadTakedown traces walls and floors on a PDF plan and adds up the load on every wall, floor by floor, down to the foundations. Choose the Pakistan (BCP 2021) · Beta region for these values, shown in kN/m² and psf, or Other to enter your own.
Try an example