Load Takedown Worked Example: Two-Storey House
25 September 2025 · 7 min read

A full load takedown for a two-storey UK house, from roof to footing, with every number shown and characteristic and design loads kept apart.
In this two-storey house, each long wall carries 47.1 kN/m characteristic (64.8 kN/m at ULS) at the top of its footing, and each end wall carries 21.6 kN/m (29.2 kN/m at ULS). This article shows where every one of those numbers comes from: plan markup, area loads, loaded widths, wall self-weight, a running total down the wall, and a check that the totals balance.
The house is deliberately simple, so the method is easy to follow. The hand takedown guide covers the same steps on a plan with an internal wall and a beam, and the last section below lists what a real house usually adds.
What does the house look like?
A rectangular two-storey house, 10.0 m long and 6.0 m wide, with a flat roof. The roof and the first floor both span 6.0 m between the two long walls, W1 and W2. The end walls, W3 and W4, run parallel to the span.
The assumptions, written down before the numbers:
- One-way spans. The roof joists and the precast first floor span one way, from W1 to W2. Nothing spans onto W3 or W4.
- Simply supported. Each span sits on its two walls, so half the load goes to each.
- Spans measured centre to centre of walls. Slightly longer than the clear span, so slightly conservative.
- Openings ignored. Taking the full wall height is conservative for self-weight. Point loads at the sides of openings are a separate check.
- The ground floor bears on the ground. It does not load the walls, so it drops out of the takedown.
- Gravity loads only. Wind and other horizontal loads are dealt with separately.
What loads go on the roof and the floor?
Build each area load up from the construction, and keep permanent (Gk) and imposed (Qk) loads in separate columns. Imposed load is the load from use: people, furniture, storage, maintenance.
| Element | Build-up | Gk (kN/m²) | Qk (kN/m²) |
|---|---|---|---|
| Flat roof | Timber joists, warm deck, membrane, ceiling | 0.9 | 0.6 |
| First floor | Beam and block with screed, finishes and ceiling | 5.0 | 2.0 |
| External walls | Brick and 100 mm medium dense block cavity wall, plastered | 3.6 per m² of wall | none |
Where the numbers come from:
- Roof Qk = 0.6 kN/m² is the UK National Annex value for a roof not accessible except for maintenance. At low altitude in much of the UK the snow load on a flat roof is less than this, so 0.6 governs. On higher or exposed sites, check the UK snow load.
- Floor Gk = 5.0 kN/m² covers beam and block with screed (typically 3.5 to 4.5 kN/m²) plus finishes and a ceiling, with a little margin. See typical UK floor and roof loads.
- Floor Qk = 2.0 kN/m² is 1.5 kN/m² for domestic use plus 0.5 kN/m² for light movable partitions.
- Wall 3.6 kN/m² comes from the wall self-weight table.
These are typical values; check them against the actual build-up with a competent engineer before using them for design.
How much floor does each wall carry?
For a simply supported one-way span, each wall carries the strip of floor between itself and midspan. That strip's width is the loaded width: half the span.
Loaded width to W1 = 6.0 / 2 = 3.0 m
Roof to W1: Gk = 3.0 × 0.9 = 2.7 kN/m Qk = 3.0 × 0.6 = 1.8 kN/m
Floor to W1: Gk = 3.0 × 5.0 = 15.0 kN/m Qk = 3.0 × 2.0 = 6.0 kN/m
This is the same as the end reaction of a simply supported beam, w × L / 2, worked out for a 1 m wide strip of floor. W2 gets exactly the same, because the house is symmetrical.
How do the loads add up down the wall?
Start at the roof and work down. At each level, add whatever lands on the wall there, plus the wall itself between that level and the next. The wall is 2.7 m per storey, and 0.6 m from the ground floor down to the top of the footing.
Wall self-weight per storey = 3.6 × 2.7 = 9.72 ≈ 9.7 kN/m
Wall below ground floor = 3.6 × 0.6 = 2.16 ≈ 2.2 kN/m
The running total for W1 (and W2), in kN/m:
| Level | Added Gk | Added Qk | Running Gk | Running Qk |
|---|---|---|---|---|
| Roof | 2.7 | 1.8 | 2.7 | 1.8 |
| First-storey wall | 9.7 | 12.4 | 1.8 | |
| First floor | 15.0 | 6.0 | 27.4 | 7.8 |
| Ground-storey wall | 9.7 | 37.1 | 7.8 | |
| Wall below ground floor | 2.2 | 39.3 | 7.8 |
So at the top of the footing:
Characteristic = 39.3 + 7.8 = 47.1 kN/m
Wall self-weight is 21.6 of the 39.3 kN/m permanent load, more than half of it. It is the part people most often leave out.
What do the end walls carry?
W3 and W4 run parallel to the span, so in this one-way scheme no roof or floor lands on them. They carry their own weight only:
Gk = 9.7 + 9.7 + 2.2 = 21.6 kN/m Qk = 0
In practice the edge joist or the last floor unit sits right next to an end wall, and some engineers give end walls a nominal strip of floor (0.5 m, say) to cover that. It makes little difference here, but write down which way you went.
What are the design loads?
The 47.1 and 21.6 kN/m are characteristic loads. Use them for the bearing pressure check against a presumed allowable pressure. For ultimate limit state (ULS) design of the footing or the masonry, factor them with 1.35 on permanent and 1.5 on all imposed loads. This is the simple form of BS EN 1990 expression 6.10, with no ψ0 reduction on the roof load, so it is slightly conservative:
W1, W2: 1.35 × 39.3 + 1.5 × 7.8 = 53.1 + 11.7 = 64.8 kN/m
W3, W4: 1.35 × 21.6 = 29.2 kN/m
The UK National Annex also allows expressions 6.10a and 6.10b, which usually give a slightly lower figure. Characteristic vs design loads works through both on a similar wall. Whichever you use, keep the characteristic and design columns separate and labelled.
Do the totals balance?
Every kilonewton put onto the building has to arrive at a footing. Compare the total load applied with the total of line load times wall length:
Applied: roof 60 m² × 1.5 = 90 kN
floor 60 m² × 7.0 = 420 kN
walls 32 m × 21.6 = 691 kN
total = 1201 kN
Footings: W1, W2 2 × 10 × 47.1 = 942 kN
W3, W4 2 × 6 × 21.6 = 259 kN
total = 1201 kN
The two totals agree, so nothing has been lost or counted twice. On a bigger plan this check is the quickest way to catch a missed strip or a floor given to two walls. The load takedown checking guide has more checks like it.
What does this mean for the footings?
As a first look, put W1 on a 600 mm wide strip footing:
Bearing pressure = 47.1 / 0.6 = 78.5 ≈ 79 kN/m²
Plus footing and backfill, roughly 20 kN/m² → about 99 kN/m² gross
That is at the bottom of the 100 to 150 kN/m² often presumed for firm clay, so a 600 mm strip is a reasonable starting point but has little margin. The site investigation decides the real allowable pressure. Foundation load from a wall goes further into footing sizing.
What did this example leave out?
A real house adds things this box does not have. Each one changes the numbers, and some change the method:
- Internal loadbearing walls. A wall with floor on both sides takes half of each span, and usually carries more than the external walls. The hand takedown guide works one through.
- Joists continuous over a wall. The middle support takes about 25% more than the half-and-half split. See one-way spans.
- Two-way slabs. A concrete slab supported on all four sides and less than about 2:1 in plan spans both ways. See two-way floor loads.
- Beams over openings. They turn line loads into point loads at the bearings. See steel post point loads and beam to foundation.
- Walls that do not line up. An upper wall that is not over a wall below is supported by the floor, which distributes its load sideways to the walls either side. See offset walls.
- Pitched roofs. Trussed rafters normally span onto the external walls only, and roof dead load is converted from slope to plan.
Free load takedown spreadsheet
SLS and ULS line loads for every wall, a UK load library and a footing width guide. Free Excel file, no account.
FAQ
What is a load takedown worked example?
It is a full takedown on one building with every number shown: the plan marked up, area loads built up, loaded widths worked out, area loads turned into line loads, wall self-weight added, and a running total carried down to a foundation line load for each wall. This one uses a simple two-storey UK house.
How long does a manual load takedown take?
For a simple two-storey house, an hour or two by hand once the plan is marked up. Most of the time goes on the markup and on keeping track of every wall, not on the arithmetic. A spreadsheet or software helps most with the bookkeeping.
Which loads did this example use?
A flat roof at 0.9 kN/m² permanent plus 0.6 kN/m² imposed, a beam and block first floor at 5.0 kN/m² permanent plus 2.0 kN/m² imposed (including partitions), and cavity walls at 3.6 kN/m² of wall. For a real job, build the loads up from the actual construction using typical UK floor and roof loads and wall self-weights.
Should the foundation load be characteristic or factored?
Both, for different checks. Compare the characteristic load (47.1 kN/m here) with the allowable bearing pressure. Use the factored ULS load (64.8 kN/m) to design the footing itself, for example its bending and shear. Keep the two in separate columns so they cannot be mixed up.
Is a load takedown enough for building control?
It is the starting point, not the whole submission. Building control will want the foundation and member designs that use these loads, checked against the relevant Eurocodes and signed off by someone competent to do so.
If you would rather not repeat this for every wall, LoadTakedown imports each PDF page as a level, lets you trace walls and spans over the drawing, and carries the loads down level by level with running totals, keeping characteristic and design loads apart. For a free starting point, there is also a load takedown spreadsheet.
Sketch your structure straight onto your drawings and get tributary loads for every wall and level, instantly.
Try the example in the app