The 45° Rule: Triangular and Trapezoidal Loads from Two-Way Slabs
9 October 2026 · 7 min read

How a slab supported on four walls splits its load with 45° lines, with the triangle and trapezoid formulas and a 4 × 6 m slab worked through.
When a slab is supported on all four sides and is less than about twice as long as it is wide, it spans both ways. To share its load between the four supporting walls, draw a line at 45° in from each corner. The two lines from each short wall meet at a point, and a ridge line joins those two points along the middle of the panel. Each short wall gets a triangle of slab and each long wall gets a trapezoid. Each wall's load is the area of its shape times the slab load.
That is the 45° rule. It is the two-way version of the half-span loaded width you use for one-way floors, and it is how the tributary regions are drawn on a rectangular two-way panel.
When does a floor span two ways?
Most UK house floors span one way. Timber joists, beam and block, and precast planks all carry load in one direction only, to the two walls at their ends, however the room is shaped. The 45° rule does not apply to them.
It applies to:
- In-situ concrete slabs supported on four sides, where the longer span is no more than about twice the shorter one. Eurocode 2 (BS EN 1992-1-1, clause 5.3.1(5)) lets you treat a slab as one-way when the ratio is greater than 2, or when two opposite edges are unsupported.
- Hipped roofs with equal pitches, where the hips run at 45° on plan. More on that below.
If the slab is more than twice as long as it is wide, treat it as one-way across the short span. The end walls then pick up only a small amount near the corners. Ignoring it is conservative for the long walls, but give the end walls a nominal allowance if they are part of the load path.
The formulas
Take a panel with short side lx, long side ly and a uniform load w in kN/m².
Short walls (triangle). The triangle has base lx and height lx / 2.
Peak line load = w × lx / 2
Total load = w × lx² / 4
Average line load = w × lx / 4
Long walls (trapezoid). The trapezoid has parallel sides ly and ly − lx, and height lx / 2.
Peak line load = w × lx / 2
Total load = w × lx × (2·ly − lx) / 4
Average line load = total / ly
Two triangles plus two trapezoids add up to w × lx × ly, the whole panel. That is worth checking every time.
For a load takedown to a strip footing, the average line load is what you want: it is the total load spread evenly along the wall, and the wall below spreads it that way anyway. The peak matters for checking the masonry at the middle of the wall, and the shape matters if the support is a beam (see below).
Worked example: 4.0 × 6.0 m slab
A concrete first floor panel 4.0 m by 6.0 m, supported on four walls. Characteristic loads are 5.0 kN/m² dead (slab, screed and finishes) and 1.5 kN/m² imposed, so w = 6.5 kN/m². No partition allowance is included in this example; add 0.5 kN/m² to the imposed load if the floor has movable partitions. These are typical values; check with a competent engineer for your own build-up. The ratio is 6.0 / 4.0 = 1.5, so it spans two ways.
Short walls, 4.0 m long:
Peak = 6.5 × 4.0 / 2 = 13.0 kN/m
Total = 6.5 × 4.0² / 4 = 26.0 kN
Average = 26.0 / 4.0 = 6.5 kN/m
Long walls, 6.0 m long:
Peak = 6.5 × 4.0 / 2 = 13.0 kN/m
Total = 6.5 × 4.0 × (12.0 − 4.0) / 4 = 52.0 kN
Average = 52.0 / 6.0 = 8.7 kN/m
Check: 2 × 26.0 + 2 × 52.0 = 156 kN, and 6.5 × 4.0 × 6.0 = 156 kN. It balances.
In the takedown, keep dead and imposed separate as usual: multiply the averages by 5.0 / 6.5 and 1.5 / 6.5 to split them. On a long wall that gives 6.7 kN/m dead and 2.0 kN/m imposed.
How much difference does it make?
If you treated the same slab as one-way across the 4.0 m span, each long wall would take half the span along its whole length: 6.5 × 2.0 = 13.0 kN/m, or 78 kN per wall, and the short walls would take nothing.
| Wall | One-way (kN) | Two-way, 45° rule (kN) |
|---|---|---|
| Each long wall | 78 | 52 |
| Each short wall | 0 | 26 |
The 45° rule moves a third of each long wall's load onto the short walls. Treating a two-way slab as one-way is conservative for the long walls but unconservative for the short walls, which can end up with footings sized for their self-weight alone. If the short walls are where the slab really bears, they need that load.
What if the wall is a beam?
If a support is a beam rather than a wall on a footing, its bending moment depends on the shape of the load, not just the total. The usual approach is an equivalent uniform load that gives the same midspan moment in a simply supported beam:
Triangle (beam span lx): w_eq = w × lx / 3
Trapezoid (beam span ly): w_eq = (w × lx / 2) × (1 − lx² / (3 × ly²))
Both come from matching the midspan moment, w_eq × L² / 8, to that of the triangle or trapezoid. For the 6.0 m long side in the example: 13.0 × (1 − 16 / 108) = 11.1 kN/m. For the 4.0 m short side: 6.5 × 4.0 / 3 = 8.7 kN/m. That is less than the 13.0 kN/m peak, but more than the 8.7 kN/m average. Use the average for reactions and footings, and the moment equivalent for sizing the beam. Using the average for bending undersizes the beam. These equivalents are for a simply supported beam; a continuous beam needs its own analysis.
Unequal edges
The 45° lines assume every edge has the same support condition. When one edge is continuous over a wall and the next is simply supported, the continuous edge is stiffer and attracts more of the load. Design aids handle this with shear coefficients. For example, BS 8110-1 Table 3.15 gives shear force coefficients for rectangular panels with different edge conditions. BS 8110 has been withdrawn, but its tables are still reproduced in Eurocode 2 design guides. For a first-pass takedown the 45° split is normally close enough, but note that it is an approximation, and check the stiffer edges more carefully.
Hipped roofs use the same shapes
On a hipped roof with the same pitch on every slope, the hips run at 45° on plan. So for a traditional cut roof, where the rafters and jack rafters bear on wall plates all round, the end walls carry a triangle of roof and the side walls carry a trapezoid, exactly as for a two-way slab. Use the same formulas with the roof load per square metre of plan area.
Take a house 8.0 m by 10.0 m with a tiled roof at 1.5 kN/m² on plan (0.9 dead + 0.6 imposed, characteristic). Here lx = 8.0 and ly = 10.0:
End walls (triangle): 1.5 × 8.0² / 4 = 24 kN, 24 / 8.0 = 3.0 kN/m
Side walls (trapezoid): 1.5 × 8.0 × (20.0 − 8.0) / 4 = 36 kN, 36 / 10.0 = 3.6 kN/m
Check: 2 × 24 + 2 × 36 = 120 kN = 1.5 × 8.0 × 10.0
The same roof with gables would put 1.5 × 4.0 = 6.0 kN/m (60 kN) on each side wall and no roof load on the end walls. Strictly, the hip rafters deliver part of the load as a point load at each corner, but a corner sits on both walls' footings, so the totals still hold for a takedown.

Two cautions:
- Trussed hipped roofs don't work like this. The hip end is usually carried by a girder truss, which puts a point load on each side wall where it bears. The 45° picture hides that point load, so get the truss layout from the supplier before you finalise the takedown.
- Unequal pitches move the hips off 45°. Take the hip lines from the roof plan and draw the shapes to scale.
Do not confuse the 45° rule on a slab with the load triangle above a lintel. That describes how masonry arches over an opening, which is a different mechanism with its own rules.
FAQ
What is the 45 degree rule for slabs?
For a slab supported on four sides, draw lines at 45° from each corner until they meet. The slab inside each shape is carried by the adjacent wall or beam: a triangle on each short side, a trapezoid on each long side. It is a simple way to split a two-way slab's load between its supports.
When is a slab one-way or two-way?
A slab supported on four sides spans two ways when its longer span is no more than about twice its shorter span. Eurocode 2 treats it as one-way when the ratio exceeds 2, or when two opposite edges are unsupported. Timber joists, beam and block, and precast planks always span one way.
How do I convert a triangular load to a UDL?
It depends what for. For a footing or a reaction, use the average: total load divided by length, which is w × lx / 4 for the triangle. For bending in a simply supported beam, use w × lx / 3, which gives the same midspan moment as the triangle.
Does the 45 degree rule apply to timber floors?
No. Timber joists only span one way, to the walls or beams at their ends. Use the half-span loaded width for each support. The 45° rule is for two-way concrete slabs and for the plan shape of equal-pitch hipped roofs.
LoadTakedown shows each wall's tributary region over your PDF and carries the loads down to the footings. Try it at LoadTakedown.
Sketch your structure straight onto your drawings and get tributary loads for every wall and level, instantly.