Typical UK Floor and Roof Loads: Dead and Imposed (kN/m²)
10 October 2026 · 9 min read

Typical UK floor and roof loads in kN/m²: imposed values from the National Annex, dead loads built up layer by layer, and a loft conversion worked through.
For a typical UK house, a timber floor carries about 0.5 to 0.8 kN/m² dead load and 1.5 kN/m² imposed load, plus a partition allowance of 0.5 to 0.8 kN/m². A 150 mm concrete slab with screed is about 5.0 to 5.5 kN/m² dead. A concrete-tiled pitched roof is about 0.9 kN/m² dead on plan, with 0.6 kN/m² imposed up to 30° pitch or the site snow load if that is larger. All of these are characteristic values, before any safety factors.
Search results for this question mix codes from several countries and quote kg/m² next to kN/m² as if they were the same. This page sticks to UK practice: BS EN 1991-1-1 with its UK National Annex. The values are typical, for early design. Check them against the actual build-up and products with a competent engineer.
What are the typical loads at a glance?
| Element | Dead load (kN/m²) | Imposed load (kN/m²) |
|---|---|---|
| Timber joist floor, boards and plasterboard ceiling | 0.5 to 0.8 | 1.5, plus partitions |
| Beam and block floor with screed | 3.5 to 4.5 | 1.5, plus partitions |
| 150 mm solid concrete slab, 50 to 65 mm screed, finishes | 5.0 to 5.5 | 1.5, plus partitions |
| Pitched roof, concrete interlocking tiles or slate, on plan | 0.7 to 1.1 | 0.6 up to 30° pitch, less above |
| Pitched roof, plain tiles, on plan | 1.1 to 1.5 | 0.6 up to 30° pitch, less above |
| Flat roof, timber warm deck | 0.5 to 0.9 | 0.6 (not accessible) |
| Ceiling joists under an unused loft | about 0.25 | about 0.25 (light storage) |
Snow replaces the roof imposed load if it is larger. It is never added to it. Manufacturer data beats any table in a blog post.
See these loads carried down a real house, wall by wall, to the foundations.
Open the example houseWhat imposed load should I use for a floor or roof?
Imposed load (a variable action in Eurocode terms, and called live load in US practice) depends on how the space is used, not on what the floor is made of. The values below are from BS EN 1991-1-1 with its UK National Annex. Each category has a uniformly distributed load, qk, and a concentrated load, Qk. You check them separately, never together.
| Use | Category | qk (kN/m²) | Qk (kN) |
|---|---|---|---|
| All areas within a single family dwelling: rooms, kitchens, stairs and landings | A | 1.5 | 2.0 |
| Offices | B | 2.5 | 2.7 |
| Retail shops | D | 4.0 | 3.6 |
| Roofs not accessible except for maintenance, pitch below 30° | H | 0.6 | 0.9 |
| Same, pitch 30° up to 60° | H | 0.6 × (60 − α)/30 | 0.9 |
| Same, pitch 60° or more | H | 0 | 0.9 |
Source: UK National Annex to BS EN 1991-1-1 (roofs from Table NA.7). The roof values act on plan: BS EN 1991-1-1 relates them to the projected area of the roof, and the annex says to apply them vertically. Check the full tables for sub-categories. Communal stairs, balconies, assembly areas and car parks all have their own, higher values.
Three points catch people out:
- The concentrated load acts on a small square. The Eurocode area is 50 mm by 50 mm. It checks the local strength of the boards or deck, and it can govern a short joist, so do not ignore it.
- Roof imposed load and snow are never added together. Use whichever is larger. At a 35° pitch the maintenance load drops to 0.6 × 25/30 = 0.50 kN/m².
- Partitions are separate. Floors with movable partitions need an extra allowance, added to the imposed load. BS EN 1991-1-1 (clause 6.3.1.2) gives 0.5 kN/m² for partitions weighing up to 1.0 kN/m of wall, 0.8 kN/m² up to 2.0 kN/m, and 1.2 kN/m² up to 3.0 kN/m. A timber stud partition 2.4 m high weighs about 0.7 to 1.0 kN/m, so it falls in the first band. Blockwork and other heavy or fixed partitions are not covered by the allowance. Take them as a line load where they stand, as a dead load.
What are typical dead loads for floors?
Dead load (permanent load) is the weight of the structure and finishes. Build it up layer by layer from unit weights. BS EN 1991-1-1 Annex A gives 24 kN/m³ for normal weight concrete, plus 1 kN/m³ for normal reinforcement, so 25 kN/m³ for reinforced concrete. Cement mortar is 19 to 23 kN/m³, and 22 kN/m³ is a common figure for sand and cement screed.
The floor in the diagram works out as follows:
Floor finish 0.10
22 mm chipboard 0.15
47 × 220 joists at 400 c/c 0.11 (0.047 × 0.22 × 4.2 / 0.4)
Insulation and services 0.10
Plasterboard and skim ceiling 0.15
Dead load Gk = 0.61 kN/m²
Imposed 1.5 + partitions 0.5 Qk = 2.0 kN/m²
Characteristic total = 2.61 kN/m²
| Floor build-up | Dead load (kN/m²) |
|---|---|
| Timber joists at 400 centres, 22 mm boards, 12.5 mm plasterboard ceiling | 0.5 to 0.8 |
| Solid concrete slab, per 100 mm of thickness (at 25 kN/m³) | 2.5 |
| 150 mm solid slab | 3.75 |
| 200 mm solid slab | 5.0 |
| Sand and cement screed, per 50 mm (at 22 kN/m³) | 1.1 |
| Beam and block, 150 mm deep, without screed | about 2.0 to 3.0 |
| Ceiling, 12.5 mm plasterboard and skim | about 0.15 |
| Floor finishes and services allowance | 0.2 to 0.5 |
Beam and block depends on the block density and beam spacing, so use the manufacturer's data rather than the range above.
A 150 mm slab with 65 mm of screed and light finishes comes to:
3.75 + (0.065 × 22) + 0.3 = 3.75 + 1.43 + 0.3 = 5.5 kN/m²
With 50 mm of screed it is 5.15, about 5.2 kN/m². Write down the build-up you actually used. It is the part a checker will want to see.
What are typical dead loads for roofs?
Roof coverings and rafters are normally weighed per m² of roof slope. A takedown works on plan, so divide the slope value by the cosine of the pitch. At 35° that is ÷ 0.82, or about 22 per cent more. The ceiling is already flat, so it goes in on plan with no conversion.
On the slope:
Concrete interlocking tiles 0.45
Battens and membrane 0.05
Trussed rafters 0.10
Sum = 0.60 kN/m² on slope
On plan:
0.60 / cos 35° = 0.60 / 0.82 = 0.73
Ceiling and insulation 0.17
Dead load Gk = 0.90 kN/m² on plan
| Roof build-up | Dead load (kN/m²) |
|---|---|
| Concrete interlocking tiles with battens and membrane, on slope | 0.45 to 0.6 |
| Clay or concrete plain tiles with battens and membrane, on slope | 0.7 to 0.9 |
| Natural slate with battens and membrane, on slope | 0.3 to 0.45 |
| Trussed rafters or cut rafters, on slope | 0.1 to 0.15 |
| Ceiling: plasterboard, skim and insulation, on plan | 0.15 to 0.25 |
| Flat roof, timber joists, warm deck with felt or single ply | 0.5 to 0.9 |
These ranges are assembled from typical product weights and the unit weights in BS EN 1991-1-1 Annex A. Tile weights vary a lot between products, so check the manufacturer's data sheet. Plain tiles are much heavier than interlocking tiles because they overlap more, and a plain-tiled roof is often 1.1 to 1.5 kN/m² on plan.
If a flat roof has gravel ballast or a green roof, add it. 50 mm of gravel ballast is about 1 kN/m², and a green roof can be several times more when saturated.
How does snow fit in?
Snow is a variable load on the roof, like the maintenance load, and you use whichever of the two is larger. It is site-specific, because it depends on the snow zone and the altitude, and it comes from BS EN 1991-1-3 and its UK National Annex.
For a 35° roof on a lowland site with a ground snow load of 0.50 kN/m², the roof snow load is 0.67 × 0.50 = 0.33 kN/m² on plan. The maintenance load at that pitch is 0.50 kN/m², so it governs. On higher ground or a shallower roof, snow can be the larger of the two. The UK snow load article works through the calculation, including drifts against walls and parapets.
Worked example: converting a loft
The house has existing ceiling joists spanning 4.0 m, and the client wants to use the loft as a bedroom. Those joists were sized as a ceiling with light storage, so the question is how much more load the floor now has to carry.
Existing ceiling joists (loft not used, light storage):
Dead = 0.25 kN/m²
Imposed = 0.25 kN/m²
Total = 0.50 kN/m² characteristic
ULS = 1.35 × 0.25 + 1.5 × 0.25 = 0.71 kN/m²
New loft floor (bedroom, domestic category A):
Dead = 0.65 kN/m² (boards, joists, ceiling, insulation)
Imposed = 1.5 + 0.5 = 2.0 kN/m² (floor plus light partition allowance)
Total = 2.65 kN/m² characteristic
ULS = 1.35 × 0.65 + 1.5 × 2.0 = 3.88 kN/m²
The design load goes up by a factor of about 5.5 (3.88 / 0.71). That is why existing ceiling joists are almost never reused as the new floor. New, deeper floor joists go in, usually supported by new steel beams or by the existing walls through padstones.
Joists spanning 4.0 m deliver half the span to each support, so the characteristic line load on each wall is:
Line load = 2.0 m × 2.65 = 5.3 kN/m characteristic
That is before the extra roof loads, any dormer, and any steel beam reactions picked up on the way. Check the walls and foundations below, not just the joists. The loft conversion loads article carries on from here to the new steels.
Put these loads on your own drawings and see the new floor load reach every wall and foundation below.
Try the example in the appCharacteristic or design load?
Everything in the tables above is characteristic: the unfactored value. For ultimate limit state (ULS) checks, the usual starting point is 1.35 × permanent plus 1.5 × variable (expression 6.10 of BS EN 1990, with one variable action). The UK National Annex also allows expressions 6.10a and 6.10b, which usually give a slightly lower figure. For serviceability checks such as deflection, and for bearing pressure under a footing, use the characteristic values. Characteristic vs design loads takes the same wall down both ways.
How do these loads feed a load takedown?
Each value above is an area load. A takedown turns it into a line load or a point load by multiplying by the width of floor or roof the element supports.
Line load (kN/m) = area load (kN/m²) × loaded width (m)
So a 1.5 kN/m² imposed load on a floor spanning 4.0 m gives 1.5 × 2.0 = 3.0 kN/m imposed on each wall, before dead load and wall self-weight. The manual load takedown article walks from roof to foundation, the loaded width article covers cantilevers, continuity and awkward plans, and wall self-weight gives the masonry figures to add at each storey.
Build up each area load from its layers once, write it on the sheet with its source, and reuse it everywhere. Most takedown errors come from mixing up the loads at this stage, not from the arithmetic after it.
If you would rather not repeat this for every wall on every level, you can do the whole building in LoadTakedown, where each floor and roof carries its own build-up and the loads accumulate down the walls for you.
Free load takedown spreadsheet
SLS and ULS line loads for every wall, a UK load library and a footing width guide. Free Excel file, no account.
FAQ
What is the imposed load on a domestic floor in the UK?
The UK National Annex to BS EN 1991-1-1 gives 1.5 kN/m² for floors in a single family dwelling (category A), with a 2.0 kN concentrated load checked separately. Add an allowance for movable partitions, usually 0.5 kN/m² for timber stud partitions. Stairs and landings inside the house take the same 1.5 kN/m². Communal stairs and balconies have higher values.
What is the dead load of a timber floor in kN/m²?
A typical timber joist floor with 22 mm boards and a plasterboard ceiling weighs 0.5 to 0.8 kN/m². Adding up the layers of a common build-up gives about 0.6 kN/m². Add more for heavy finishes such as tiles on a screed, deeper joists, pugging or a second layer of plasterboard.
How much does a concrete slab weigh per m²?
Reinforced concrete is taken as 25 kN/m³, so a slab weighs 2.5 kN/m² for every 100 mm of thickness. A 150 mm slab is 3.75 kN/m² and a 200 mm slab is 5.0 kN/m². Add screed (about 1.1 kN/m² per 50 mm) and finishes. If you need kg/m², multiply kN/m² by about 102, but design in kN.
What load can a loft floor take?
It depends on how the joists were designed. Ceiling joists under an unused loft are usually sized for light storage, about 0.25 kN/m², which does not allow for a bedroom or heavy storage. A habitable floor needs 1.5 kN/m² plus partitions, so a structural check or new joists are almost always needed.
Do I add snow load to the roof imposed load?
No. The roof maintenance load (0.6 kN/m² up to 30° pitch) and snow are never combined. Use whichever is larger. Snow depends on the site's snow zone and altitude and comes from BS EN 1991-1-3 and its UK National Annex. Check the 0.9 kN concentrated load on the roof covering and battens as well.